INSTALLATION
Traps should be installed in easily accessible position and location for servicing. The maximum differential pressure stamped on product name plate must be higher than the maximum differential pressure across the trap.
1.Pitch all horizontal inlet lines towards the stream trap to help eliminate potential water hammer problems.
2.A dirt pocket and strainer (with blow down) should always be provided before trap.
3.Union fittings or flange connection and shut off valves should be installed on both sides of trap for ease of servicing and trap testing.
4.Install a test valve in outlet pipe and cap it. This allows trap to be tested.
5.Blowdown piping using full steam pressure for (5) five minutes prior to service. This cleaning process will remove debris from piping.
6.Perform maintenance and cleaning 2/3 days after startup until system is clean. Then perform maintenance every 6/12 months in normal operation.
MAINTENANCE
With regular check and proper maintenance you get optimum performance and a long life service from our product. The mechanism should be inspected periodically and all dirt should be removed from working parts. Worn parts must be replaced. Always renew the gasket whenever you disassemble the steam trap.
SPARE PARTS | ||
No | Description | Material |
1 | BODY | CARBON STEEL WCB |
2 | DISC | 2Cr13 |
3 | SEAT | 2Cr13 |
4 | SCREEN | STAINLESS STEEL 304 |
5 | Bİ-METAL METAL SHEET | FPA206-78 |
6 | DISC GASKET | STAINLESS STEEL 304 |
7 | BONNET | CARBON STEEL WCB |
8 | GASKET | 304+GRAPHITE |
9 | BONNET BOLT | 35 |
10 | BODY GASKET | STAINLESS STEEL 304 |
11 | DISC STOPPER | 2Cr13 |
12 | BONNET STUD | SAE Gr.5 |
DIMENSIONS | |||||||
Size | L | H1 | H2 | D | D1 | D2 | N-Ø |
DN15 | 150 mm | 22 mm | 100 mm | 95 | 65 | 45 | 4-14 |
DN20 | 150 mm | 22 mm | 100 mm | 105 | 75 | 58 | 4-14 |
DN25 | 160 mm | 22 mm | 100 mm | 115 | 85 | 68 | 4-14 |
DN32 | 210 mm | 40 mm | 140 mm | 140 | 100 | 78 | 4-18 |
DN40 | 210 mm | 40 mm | 140 mm | 150 | 110 | 88 | 4-18 |
DN50 | 230 mm | 40 mm | 140 mm | 165 | 102 | 102 | 4-18 |
CONNECTION | FLANGED | |||||
Sizes | DN15 | DN20 | DN25 | DN32 | DN40 | DN50 |
Wieghts (KGS) | 4 | 4,8 | 5,2 | 6,3 | 7,3 | 9,4 |
OPERATING CONDITIONS | |
MAX. ALLOWABLE PRESSURE PMA (BAR) | 40 |
MAX. ALLOWABLE TEMPERATURE TMA (ºC)ºC) | 300 |
MAX. DIFFERENTIAL PRESSURE PMD (BAR) | 21 |