FLOAT &THERMOSTATIC STEAM TRAP

FLOAT &THERMOSTATIC STEAM TRAP

FLOAT &THERMOSTATIC STEAM TRAP
FLOAT &THERMOSTATIC STEAM TRAP
FLOAT &THERMOSTATIC STEAM TRAP
FLOAT &THERMOSTATIC STEAM TRAP
FLOAT &THERMOSTATIC STEAM TRAP
FLOAT &THERMOSTATIC STEAM TRAP
Product Information
Product Name - FLOAT &THERMOSTATIC STEAM TRAP
MODEL NST-43FTVP
Product Category - · Nordsteam Steam and Flow Control Group · Steam Traps · Float & Thermostatic Steam Traps
Product Brand - Nordsteam

Product Features
FLOAT &THERMOSTATIC STEAM TRAP

The body of NST-43FTVP series of ball float traps with thermostatic air vent is made of either cast iron or stainless steel. All float traps are furnished with an integral balance pressure type thermostatic air vent.The NST-43FTVP series is installed horizontally in line connections.

INSTALLATION
Traps should be installed in easily accessible position and location for easy servicing. The maximum differential pressure which is stamped on product name plate must be bigger than the maximum differential pressure of the whole system. Be sure to install trap horizontally to ensure proper operation.
1.Install the trap below and close to the equipment which will drain and avoid long lenghts of horizontal piping ahead of trap.
2.Pitch all horizontal inlet lines towards the stream trap to help eliminate potential water hammer problems.
3.A strainer should always be installed ahead of trap.
4.Union fittings or flange connection and shut off valves should be installed on both sides of trap for ease of servicing and trap testing.
5.Install a test valve in outlet pipe and cap it,which allows trap to be tested. Cap is used as safety precaution when unit is not being tested.
6.Blowdown piping using full steam pressure for 5 minutes prior to service. This cleaning process will remove debris from the pipe-line.
7.Perform maintenance and cleaning 2/3 days after start-up until system is clean. Then perform maintenance every 6/12 months once in normal operation.

MAINTENANCE
With timely check-up, regularly and properly maintenance, NORDSTEAM NST43FTVP series will provide optimum performance and long life cycle.The internal components of steam trap can be replaced without removing the trap from the line. The trap mechanism should be inspected periodically and all dirt removed from working parts. Worn parts must be replaced with new ones. Whenever the bonnet of steam trap is taken apart, always replace the gasket of the bonnet, with a new one.

 

SPARE PARTS
No Description Material
1 Cover ENGJS 400 18 DIN 1693 GGG40.3
2 Body ENGJS 400 18 DIN 1693 GGG40.3
3 Valve Seat Stainless Steel
4 Water Hammer Preventer Stainless Steel
5 Valve Seat Bolt SS316 & /SS304
6 Valve Seat Nut SS316 & SS304
7 Shaft SS316 & SS304
8 Bonnet Gasket

NON ASBESTOS GASKET

9 Shaft Gasket SS316 & SS304
10 Pin SS316 & SS304
11 Thermostatic Element  Stainless Stell 304
12 Cover Nut SAE Gr.5
13 Cover Stud SAE Gr.5
14 Float Handle Stainless Steel
15 Float Ball Stainless Steel

DIMENSIONS
Size L H D D1 D2 N-Ø
DN32 230 mm 318 mm 140 100 78 4*18
DN40 230 mm 327 mm 150 110 88 4*18
DN50 230 mm 334 mm 165 125 102 4*18

CONNECTION FLANGED
Sizes  DN32 DN40 DN50
Weights (KG)  27 30 30,5

OPERATING CONDITIONS
Max. Allowable Pressure PMA (bar) 24
Max. Allowable Temperature TMA (ºC) 220
Max. Operating Pressure PMO (bar) 16
Max. Differential Pressure PMD (bar) 4,5 , 10 , 14