FREE FLOAT STEAM TRAP WITH THERMOSTATIC AIR VENT

NST-55FX Free float steam traps are used in the steam pipe-lines and the heating systems, paper , food, petrochemical and petroleum industries ,etc. They are especially prefered where there is need for fast heating and where heat controlling is strictly significant. It doesn’t have any wearing component chronically.Therefore, It has a long service life and notable energy savings. It starts up quickly and drains condensate continuously. Low
level noise, Easy to repair. As it has a large surface area of screen built-in , it ensures trouble free operation for a long time.They are resistant to water hammer.

INSTALLATION
Traps should be installed in easily accessible position and location for easy servicing. The maximum differential pressure which is stamped on product name plate must be bigger than the maximum differential pressure of the whole system. Be sure to install trap horizontally to ensure proper operation.
1.Install the trap below and close to the equipment which will drain and avoid long lenghts of horizontal piping ahead of trap.
2.Pitch all horizontal inlet lines towards the stream trap to help eliminate potential water hammer problems.
3.A strainer should always be installed ahead of trap.
4.Union fittings or flange connection and shut off valves should be installed on both sides of trap for ease of servicing and trap testing.
5.Install a test valve in outlet pipe and cap it,which allows trap to be tested. Cap is used as safety precaution when unit is not being tested.
6.Blowdown piping using full steam pressure for 5 minutes prior to service. This cleaning process will remove debris from the pipe-line.
7.Perform maintenance and cleaning 2/3 days after start-up until system is clean. Then perform maintenance every 6/12 months once in normal operation.

MAINTENANCE
With timely check –up, regularly and properly maintenance, NORDSTEAM NST55FX series will provide optimum performance and long life cycle. The internal components of steam trap can be replaced without removing the trap from the line. The trap mechanism should be inspected periodically and all dirt should be removed from working parts. Worn parts must be replaced with new ones. Whenever the bonnet of steam trap is taken apart always, replace the gasket of the bonnet, with a new one.

SPARE PARTS
No Description Material
1 Body Carbon Steel (WCB)
2 Screw Plug 45
3 Orifice Stopper 2Cr13
4 Orifice 2Cr13
5 Float SS 304
6 Strainer SS 304
7 Retainer Ring A3
8 Bonnet Gasket SS 304 + Graphite
9 Temperature Sensitive X-Elemen       Hastelloy
10 Air Eliminator Seat 2Cr13
11 Cleaning Plug 2Cr13
12 Bonnet Plug Steel
13 Gasket Steel
14 Bonnet Carcon Steel (WCB)
15 Stud Bold

SAE Gr.5

16 Nut

SAE Gr.5


DIMENSIONS
Size L H1 H2 D D1 D2 N-Ø
DN15 195 mm 105 mm 100 mm 95 65 45 4*14
DN20 195 mm 105 mm 100 mm 105 75 58 4*14
DN25 215 mm 115 mm 105 mm 115 85 68 4*14

CONNECTIONS FLANGED
Sizes DN15 DN20 DN 25
Weights (KG) 7,5 7,8 10

OPERATING CONDITIONS
Max. Allowable Temperature TMA (ºC)   220
Max. Operating Pressure PMO (bar) 16
Max. Differential Pressure PMD (bar) 8