Product Name - INVERTED BUCKET STEAM TRAP WITH STRAINER
MODEL NST88HSP
Product Category - · Steam and Flow Control Group · Traps · Inverted Bucket Steam
Product Brand - Nordsteam

Product Features
INVERTED BUCKET STEAM TRAP WITH STRAINER

The Inverted Bucket Steam Trap is simply an automatic valve that opens for condensate and air but closes for steam. Steam entering the inverted submerged bucket causes the bucket to float and rise , by the effect of rising, closes the valve. But meanwhile condensate begins to enter the trap and also begins filling the bucket . The filling bucket begins sinking and opening the trap valve to discharge the condensate. Nordsteam inverted bucket steam traps have frictionless leverage system that multiplies the force made by the bucket, which forces the valve to open against pressure.

INSTALLATION
Traps should be installed in easily accessible position and location for easy servicing. The maximum differential pressure stamped on product name plate must be greater than the maximum pressure differential across the trap. The trap must be installed with the body horizontally so that bucket will rise and fall vertically. The inlet and outlet connections should be in a horizontal plane for horizontal traps and a vertical plane with inlet on the bottom for vertical traps. The trap should be installed below the drain point, so that a water seal can be maintained around the open end of the bucket.

1.Install the trap below and close to the equipment which will drain condensate, avoid long lenghts of horizontal piping ahead of trap.

2.Pitch all horizontal inlet lines towards the stream trap to help eliminate potential water hammer problems.

3.All models should have a strainer installed ahead of trap.

4.Union fittings and shut off valves should be installed on both sides of trap for ease of servicing and trap testing.

5.A test and pressure relief valve should be installed to assure relief of internal pressure prior to servicing.

6.A check valve should be installed on return piping if there will be a pressurized return line or the trap drains to an over head return line.

Inverted bucket traps may need to be primed before being placed into service. Either of the following methods can be used.

1.Remove pipe plug from trap cover. Pour water into trap until full and replace pipe plug.

2.Keep return piping valve closed until trap fills with condensate, then slowly open valve.

MAINTENANCE
The trap mechanism should be inspected periodically and dirt should be removed from working parts. Worn parts must be replaced.

SPARE PARTS
No Description Material
1 Bonnet CI ASTM A48 CLASS 30
2 Body CI ASTM A48 CLASS 30
3 Valve Chrome Steel
4 Valve Seat Chrome Steel
5 Lever STAINLESS STEEL 304
6 Bucket Clip STAINLESS STEEL 304
7 Bucket STAINLESS STEEL 304
8 Thimble STAINLESS STEEL 304
9 Strainer Gasket Steel
10 Valve Clip STAINLESS STEEL 304
11 İnternal Tube Steel Pipe
12 Gasket STAINLESS STEEL 304 + Graphite
13 Bonnet Plug Steel 
14 Strainer Plug Steel
15 Strainer STAINLESS STEEL 304
16 Bonnet Bolt SAE Gr.5

DIMENSIONS
Size L L1 H H1
1/2’’ 128mm 95mm 157mm 87mm
3/4’’ 128mm 95mm 184mm 113mm
1’’  167mm 143mm 238mm 138mm
1 1/4’’ 209mm 178mm 320mm 192mm
11/2’’  250mm 220mm 396mm 248mm
2’’ 250mm 220mm 396mm 248mm

CONNECTION SCREWED BSP
Sizes 1/2" 3/4" 1" 1/4'' 11/2’’ 2’’
Weights (KG) 3,1 3,6 8,7 16,0 28 31

OPERATING CONDITIONS
Max. Allowable Pressure PMA (bar) 24
Max. Allowable Temperature TMA (ºC) 300
Max. Differential Pressure PMD (bar) 5,5 - 8
Max. Operating Pressure (bar) 16